High grade ceramic new building chimney BÜ
Assembly
Exhaust conduit for
overpressure operation
Primary Sizes |
BÜ 8 |
28 x 28 cm |
BÜ 10 |
28 x 28 cm
|
BÜ 12
|
34 x 34 cm |
BÜ i 8
|
34 x 46 cm |
BÜ i 10
|
34 x 46 cm |
BÜ i 12
|
34 x 46 cm |
CI/BÜ 1808
|
38 x 66 cm |
CI/BÜ 1810
|
38 x 66 cm |
CI/BÜ 1812
|
38 x 66 cm |
CI/BÜ 2008
|
38 x 66 cm |
CI/BÜ 2010
|
38 x 66 cm |
CI/BÜ i 1808
|
38 x 62 cm |
CI/BÜ i 1810
|
38 x 62 cm |
CI/BÜ i 1812
|
38 x 62 cm |
CI/BÜ i 2008 |
38 x 62 cm |
CI/BÜ i 2010
|
38 x 62 cm |
I stands for additional installation shaft (single-flue 8 x 24 cm, double-flue 6.5 x 20 cm). For further sizes, see Price List pp. 16 – 17; Special sizes upon request |
Application
Gas/oil condensing boilers
Chimney systems
Twin-shelled exhaust conduit, high-grade ceramic pipes, direct and counter current operation, for wet operation
Licence number
Z-7.2-3135 and Z-7.1-1512, CE identification for the high-grade ceramic pipes A1N1/A2P1/B2N1/D3P1, Heat Conduction Group IV (TR 00)
System components
High-grade ceramic pipe, length 1-1.5 m, stainless steel spacers, elastomer seals, surface-ground mantle block
Technical data
Moisture resistant for oil and gas condensing boiler technology, ambient air-independent, overpressure operation
Areas of application
Exhaust temperatures of 30 - 200° C, oil or gas
Recommended cross sections
For gas condensing boilers up to 25 kW 80 mm; calculate if over 25 kW! For oil condensing boilers up to 25 kW 80-120 mm depending on make